- The product have designed specifically to operate with strain gauge sensors such as Fast- measurement of Load cell, Pressure Transducer, LVDT, etc. The setup sequence is simple and quick using four push buttons only.
- High resolving power (16bit A/D)
- High presision (more than 0.012% F.S) and stability
- Quick sampling speed (100times/sec)
- Built-in Shunt calibration switch
- Watch dog
- Small size(96*48*128mm) / Cutting size : 92*45mm
- Weight : about 700g
- Option: Power Input 24V in accordance with customer request
Weighing
DN-10W/DN-15W
Digital indicator
Product Specifications
Specifications | Accuracy | |
---|---|---|
DN15W | DN10W | |
Application sensor | Strain guage sensor (350Ω or 700Ω) | |
Sensor authorized voltage (the number of Loadcell connection) |
DC 5V, Loadcell(350Ω) available 4 | |
Zero adjustment range | 100% F·S (Auto Zero) | |
Input signal | 0.5 ~ 3mV/V | |
Display | -19999~99999 | |
Display speed | Appox 30times/sec(Adjustment available by buff setting) | |
Character height | 7Segment 5 digit LED 14mm | |
Decimal point | Random setting available | |
A/D converter | 16bit, Max. 100 times/sec | |
D/A converter | 12bit | |
Zero variation | within 0.5μV/℃ | |
Sensitivity variation | within0.01%/℃ | |
Voltage output | DC 0~10V (4~20mA : in accordance with customer request) | |
Usage temperature range | -10℃ ~ 60℃ | |
Humidity | less than 80% RH (no dew condensation) | |
Power source used | 220V 50/60Hz (110V available by internal operation) |
220V 50/60Hz (110V available by internal operation) |
Relay output | ㆍUpper and lower limit comparison output ㆍ4 relay output ㆍContact capacity : AC 250V 5A ㆍRelay life time : more than 5,000,000times |
|
Network | RS-232C | |
Option | ㆍBCD Paralle out (OP-01) ㆍRS485 (OP-02) ㆍDAC ANALOG OUT (OP-03) |